Make energy flows transparent and verify savings
Energy monitoring shows how much energy your site consumes, when and for what purpose, how much your systems generate and whether everything is operating as planned. It answers four questions: How is the business performing compared with plan? What is causing costs? Are systems operating as intended? And can savings be verified? Without monitoring, an energy management system remains a black box and savings cannot be demonstrated.
Table of contents
Data sources
A monitoring system combines data from several sources:
- Grid-connection meters and submeters for electricity, heat, cooling, gas and compressed air
- Inverters, battery storage systems and charging points
- Production data such as unit counts or batches to put consumption into context
- Weather and price data for evaluating PV generation and tariffs
The underlying metering technology is described on the Metering & Control page.
Data quality and architecture
Dashboards are only as good as the data behind them. Consistent timestamps, clearly flagged data gaps and comprehensible naming of measurement points are essential. Abnormal values, such as a sudden zero-consumption reading, should trigger an alert instead of flowing unnoticed into the analysis. Reconciliation between the grid-connection meter and submeters reveals measurement errors.
Technically, a monitoring system consists of on-site data acquisition, a time-series database and an interface for analysis. It should also allow data export so that you are not locked into a single provider.
KPIs that matter
Not every number needs a chart. The following KPIs have proven useful in practice:
- Peak demand and the time of the peak during the billing year
- Base load outside production hours
- Specific consumption, for example kWh per production unit
- Self-consumption and self-sufficiency ratios for PV
- Storage utilization, cycles and availability
- Deviation between forecast and measured value
KPIs should always be placed in context using a comparison value: previous year, planned value or reference day.
Dashboards for different target groups
- Management: a small number of KPIs, with cost and savings trends
- Technical management: load profile, system status, alarms and deviations
- Energy managers and controlling: consumption by cost center and KPIs for reports and audits
- Operations and maintenance: fault messages and system condition
A dashboard designed for everyone is usually useful to no one. Define target groups in advance.
Monitoring PV, storage and charging infrastructure
For PV systems, monitoring compares actual generation with expected output and makes inverter failures or soiling visible. For storage systems, it shows state of charge, cycles,
efficiency and control-system interventions. For charging points, utilization, charging power and faults are the main focus. If more parameters are measured than are required for billing, malfunctions can be detected early.
Alarming
Alarms must lead to action. A small number of clearly prioritized notifications is useful: power limit exceeded, system failure, missing measurement, communication fault. Too many alarms result in none of them receiving attention. Define who receives which alert and who is responsible for responding.
CO₂ accounting and reporting obligations
Electricity-related CO₂ emissions can be estimated from consumption data by multiplying consumption by an emissions factor; which factor is permitted depends on the reporting framework. Monitoring provides the data basis that can also be used for reports under the Energy Efficiency Act and for sustainability reporting. We clarify which obligations apply to your company; see Standards & Compliance.
Verify savings
Demonstrating savings requires a comparison: consumption before and after a measure, adjusted for influences such as production volume and outside temperature. Document the baseline before implementation. This creates clarity for management, funding bodies and auditors.
Typical mistakes
- Data without ownership: no one reviews the analysis or derives actions
- Too many KPIs and dashboards
- Missing baseline for verification
- Measurement points without consistent naming
- Alarms without recipients or priorities
Phased implementation
First make the main consumers and grid connection visible, then introduce KPIs and alarms, and only afterward expand submetering and cost-center analysis. Each stage should already support concrete decisions.
Frequently asked questions
Is monitoring with 15-minute values sufficient?
Yes for billing, demand charges and daily analyses. For fault analysis and control, you need higher-resolution values that can be stored locally.
Is energy monitoring mandatory?
There is no general obligation. Depending on your energy consumption, however, the Energy Efficiency Act may require energy management systems or implementation plans, and reliable consumption data are necessary for these. We clarify the requirements for your company in the initial consultation.
Initial consultation