Without reliable measurements, there can be no forecasting, optimization or proof of savings.

Metering Concept and Control: Zähler, Smart Meter Gateway und Steuerbox richtig planen
Without reliable measurements, there can be no forecasting, optimization or proof of savings. Ohne Control technology bleiben selbst gute Analysen folgenlos. Messung und Steuerung sind deshalb die technische Grundlage jedes Energiemanagements: Zähler und Sensoren erfassen Energie und Leistung am Netzanschluss, in den Unterverteilungen und an einzelnen Anlagen, ein Steuerungssystem setzt daraus Sollwerte für Speicher, Wechselrichter, Ladepunkte, Wärmepumpen oder Prozesse um.

Table of contents
- Measuring, controlling and regulating
- Metering technology
- Metering concept for PV, storage and charging infrastructure
- Control technology
- Grid-oriented control and feed-in limitation
- Interfaces and data quality
- Economic viability
- Phased implementation
- IT security
- Typical mistakes
- Frequently asked questions
- Initial consultation
Measuring, controlling and regulating
- Measure: recording energy (kWh), power (kW), and where required reactive power, voltage, temperature or pressure
- Control: specifying a state or setpoint without feedback, such as switching off a charging station or setting a power limit for an inverter
- Regulate: continuous adjustment. The controller compares measured grid demand with the setpoint, for example 800 kW, and adjusts the storage discharge power accordingly
Metering technology
For final consumers with more than 100,000 kWh annual consumption, electricity consumption is generally measured using registered 15-minute load-profile metering (RLM). This produces 35,040 demand values per year. The highest value determines the annual demand charge in the grid fee. The load profile may show that a peak of 1,180 kW occurred at 6:15 a.m., but not which systems caused it. Submetering is required for that. The Load Profiles page explains how to evaluate your load profile.
A smart metering system consists of a modern metering device and a smart meter gateway. It transmits readings in encrypted form to authorized market participants and is a prerequisite for grid-oriented control, dynamic tariffs and time-variable grid fees. It does not replace operational submetering and is not designed to control a storage system on a second-by-second basis. For that, a separate real-time measurement at the grid connection is required. The Metering Point Operation Act provides for smart metering systems, among other cases, for final consumers with more than 6,000 kWh annual consumption and for generation systems above 7 kW, insofar as this is economically reasonable.
Different devices are used for submetering depending on the task:
- direct-connected meters for smaller feeders, usually with a Modbus or M-Bus interface
- current-transformer meters for large feeders and machines. The transformer must match the measurement task because an oversized transformer is inaccurate at partial load
- power-quality analyzers for harmonics, reactive power and voltage events, for example with large drives, converters and charging infrastructure
- sensors for heating and cooling energy, compressed air, gas or steam
If submeters are used for billing third parties, such as tenants or EV charging customers, they must comply with legal metrology requirements. For internal operational analyses, a non-certified device is often sufficient if its accuracy is adequate.
Metering concept for PV, storage and charging infrastructure
The metering concept defines which meters at which locations record which energy quantities. It is coordinated with the grid operator and metering point operator, is often part of the grid-connection application, and determines whether your project can later be billed, subsidized and controlled correctly. Typical components include:
- a bidirectional meter at the grid connection that records import and feed-in separately
- a generation meter at the PV system that makes self-consumption measurable a meter at the battery storage system for charging and discharging, important for grid charging or marketing
- meters for third-party consumers such as tenants, lessees or external charging users
- separate metering of controllable consumption devices where reduced grid fees under Section 14a EnWG are to be used
Control technology
The central control task is the power balance at the grid connection. The controller measures import or feed-in power, compares it with the setpoint and adjusts storage discharge power, inverter active power, charging-point power or the power of flexible processes. Three factors determine control quality:
- Measurement rate: second-level values are typical for a feed-in limit; 15-minute values are sufficient only for planning.
- Dead time: routing through a cloud server can add several seconds. Time-critical functions therefore belong on a local controller.
- Control reserve: a 200 kW storage system cannot by itself compensate for a peak that is 300 kW above the target value.
The grid operator, direct marketer, aggregator and your own EMS can all send control commands. Without a clear hierarchy, conflicting setpoints can arise. Protection functions and grid-operator requirements have highest priority, followed by mandatory operational criteria such as process safety or vehicle availability, and finally economic objectives. A defined fallback state must be specified for failures of communication or metering.
Grid-oriented control and feed-in limitation
For grid-oriented control, a control box is connected to the smart metering system via the gateway’s CLS channel. The control box outputs signals through relay contacts or digitally, for example via EEBUS. For businesses with an EMS, digital integration is usually preferable: the EMS receives the power limit and allocates it across the systems itself instead of switching individual devices off abruptly.
Under Section 14a EnWG, heat pumps, non-public charging points, cooling systems and electricity storage systems in the low-voltage grid are considered controllable consumption devices. The grid operator may temporarily reduce their consumption if an overload threatens; in return, a reduced grid fee applies. The Federal Network Agency defines the power threshold and the applicable tariff modules.
Controllability is also becoming mandatory on the generation side. New PV systems below 100 kW commissioned since 25 February 2025 may feed in no more than 60 percent of their installed capacity until a smart metering system with a control device is operational. Technically, a controller usually applies the limit dynamically: it measures feed-in at the grid connection and curtails the inverters only as much as necessary to avoid exceeding the limit. Self-consumption therefore remains fully usable.
Interfaces and data quality
In practice, a single protocol is rarely sufficient. A typical site combines Modbus TCP for meters and inverters, OCPP for charging infrastructure, EEBUS or relay contacts for the control box, and an interface to the cloud platform. A controller translates between these systems. When procuring equipment, require register lists, data-point lists and interface documentation to be included in the scope of delivery.
Measurement data are only as good as their quality:
- Time resolution: 15-minute averages matter for billing and demand charges; second-level values are needed for control and fault analysis. Exact 15-minute averages cannot be reconstructed from minute-level data.
- Time synchronization: submeters, controllers and the RLM load profile must use the same time base. A shift of only a few minutes makes reconciliation with the grid operator’s load profile impossible.
- Plausibility checks: data gaps must be detected and flagged. A simple check is energy-balance reconciliation: the sum of the submeters should match the grid-connection meter apart from an explainable residual.
Economic viability
Rechenbeispiel (Annahmen)
A logistics site has ten charging points rated at 22 kW each. If all vehicles charge at the start of a shift, peak demand can increase by up to 220 kW. Load management limits charging power during this period to 80 kW, thereby avoiding 140 kW of peak demand. At an assumed demand charge of €100 per kW per year, this corresponds to €14,000 per year. The vehicles are still fully charged by the next shift. The actual demand charge should be taken from your grid operator’s tariff sheet.
Mess- und Control technology kann über Modul 3 der Bundesförderung für Energie- und Ressourceneffizienz in der Wirtschaft (EEW) förderfähig sein. Der Antrag muss vor Beginn des Vorhabens gestellt werden. Mehr dazu auf der Seite Fördermittelberatung.
Phased implementation
- Baseline assessment: evaluate the RLM load profile and document existing meters and distribution structure
- Measure major consumers: install submeters on the largest feeders
- Real-time measurement at the grid connection and a local controller
- Connect controllable systems via open interfaces
- Integrate external signals: control box, dynamic tariffs, direct marketing and aggregator
IT security
An EMS intervenes directly in system control and therefore belongs to operational technology. Modbus TCP has no built-in authentication and must never be directly accessible from the internet. Recommended measures include separating office IT from operational technology, using encrypted remote access, implementing an authorization concept and maintaining controlled update management.
Typical mistakes
- Metering concept too late: meters are planned only after PV and storage have been installed, causing rework and delaying commissioning.
- Incorrectly sized current transformers: energy-balance reconciliation does not work.
- Data stored at too coarse a resolution: 15-minute peaks cannot be reconstructed.
- Control through the cloud: time-critical functions fail when the connection is lost.
- Unclear control authority: grid operator, direct marketer and EMS send conflicting setpoints.
Frequently asked questions
What is the difference between RLM and a smart metering system? Registered load-profile metering records 15-minute values for billing and demand charges. A smart metering system consists of a modern metering device and gateway and additionally enables encrypted data transmission, control via the CLS channel and time-variable tariffs. In both cases, real-time control of a storage system requires a separate measurement at the grid connection.
Initial consultation
Welche Metering technology an Ihrem Standort bereits vorhanden ist und was für ein EMS fehlt, klären wir im Initial consultation.