For businesses with demand metering, a single 15-minute interval often determines what the grid costs for the entire year. Peak shaving prevents that interval from occurring in the first place. When implemented correctly, it reduces demand charges, frees up grid-connection capacity and often requires less storage than many proposals suggest.
Optimization & Marketing
Peak Shaving: cut peak loads and permanently reduce demand charges
Peak Shaving: cut peak loads and reduce demand charges
For businesses with demand metering, a single 15-minute interval can determine a large part of annual grid fees: the year’s maximum demand. Peak shaving limits this peak using battery storage, load management or both. We use your load profile to assess whether this is economical for your site and design the solution so it reliably captures the peak even under unfavorable conditions.
Why peak loads cost money
Grid fees consist of an energy charge for consumed electricity and a demand charge based on the highest power demand of the year (Section 17 StromNEV). Demand is measured in 15-minute intervals. A year contains 35,040 such intervals, but only the highest one is relevant for the demand charge. From an annual consumption of 100,000 kWh, 15-minute load-profile metering is mandatory (Section 55 MsbG). A short peak, for example when several machines start simultaneously, can therefore create costs far out of proportion to the energy consumed during that interval.
Utilization hours are also important for determining grid fees, calculated as annual electricity consumption divided by annual peak demand. Grid fees are tiered according to utilization: with low utilization, the demand charge is higher and the energy charge lower; with high utilization, the reverse applies. Your grid operator defines the prices in its tariff sheet. We use the actual tariff for your site rather than average values.
How peak shaving works
There are three ways to reduce the peak:
- Battery storage: the battery supplies power once grid consumption reaches a defined threshold and recharges during periods of lower load.
- Load management: flexible consumers such as refrigeration systems, compressors, charging points or heat pumps are temporarily reduced or shifted. This is often the most cost-effective measure because no storage investment is required.
- Generation-side measures: a CHP unit or emergency generator can cover peaks. Photovoltaics alone do not reliably reduce peak demand because the annual maximum often occurs in the morning, evening or under cloudy conditions.
In practice, we usually combine load management and storage. The control system can work with a fixed threshold, dynamically adjust the threshold to the highest demand reached so far, or use forecasts for proactive charging. The appropriate approach depends on the load profile.
Sizing: power first, then energy
A storage system primarily needs to deliver peak power rather than large amounts of energy. We therefore proceed as follows:
- Evaluate at least twelve months of load-profile data and determine the magnitude and duration of peaks
- Define the target limit: each additional kilowatt shaved reduces demand charges, but usually requires more storage power and capacity, while the marginal benefit decreases
- Size storage power and capacity to match the longest peak
- Include reserves for rare peaks and aging
- Calculate economics using investment cost, operating cost and the actual grid tariff
Calculation example (assumptions)
Assuming a demand charge of €100 per kW per year and a peak reduction of 200 kW, the savings amount to €20,000 per year. This must be weighed against investment, maintenance, storage losses and possible changes in utilization hours. Only a calculation using your actual values shows whether the measure is worthwhile.
Technology and operation
Peak shaving works only when metering is fast and reliable. The control system needs short-interval measurements at the grid connection, synchronized with the meter’s 15-minute interval. A fallback layer, such as load shedding if the storage system fails, secures operation. IT security and time synchronization are also part of the concept. See Metering & Control and EMS & Smart Grid for more details.
Peak shaving must not create a new peak. Charging the battery too quickly at night or operating it simultaneously with charging points and heat pumps merely shifts the peak. Energy management therefore coordinates storage, photovoltaics and flexible loads. The same applies when using dynamic electricity prices: charging at low prices must never increase annual peak demand.
Legal points you should know
Businesses with an individual grid fee under Section 19(2) StromNEV, for example due to atypical grid use or a baseload profile of at least 7,000 hours and more than 10 GWh annual consumption, should check before peak shaving whether the arrangement would be affected. We clarify this before planning.
The grid-fee system is being restructured. According to the Federal Network Agency’s AgNes draft, a capacity charge is intended to apply from 2029 to consumers above 100,000 kWh. The principle of limiting demand remains relevant, so peak management will continue to have value; the precise effect depends on the final regulation. See Smart Energy Management for context.
The grid connection also matters: a storage system that reduces peak demand can relieve existing connection capacity and thereby avoid or postpone an expansion.
Typical mistakes
- Storage sized by intuition without load-profile analysis
- Peaks assessed only by magnitude, not duration and frequency
- Metering not synchronized with the billing meter, or omitted
- No fallback strategy for storage failure
- Night charging that creates a new peak
- Impact on utilization hours not calculated
- Load management not assessed as a lower-cost alternative
- Existing individual grid-fee arrangement not considered
Frequently asked questions
At what peak level does peak shaving become worthwhile?
It depends on your grid operator’s demand charge, the magnitude and duration of the peaks, and the cost of the measure. There is no universal threshold. Only the load profile shows how much demand can be reduced and across how many 15-minute intervals.
Is load management without storage sufficient?
Often yes, if enough load can be shifted briefly without affecting production or comfort. For short, high and non-shiftable peaks, storage is useful. We often combine both.
Does a photovoltaic system reduce my peak loads?
Only coincidentally. PV reduces purchased energy, but it lowers annual peak demand only if the peak occurs during sunny hours. A storage system with predictive control can reduce peaks reliably.
What happens if the battery is empty during a peak?
Grid consumption then rises above the threshold and a new annual maximum demand is created. That is why we include reserves and fallback measures such as load shedding.
Can a storage system perform several tasks?
Yes. In addition to peak shaving, it can increase self-consumption or take advantage of dynamic prices. The control system must then set priorities because peak shaving takes precedence. See Battery Storage for more details.
Initial consultation
We use your load profile to assess whether peak shaving is worthwhile for your site. Get in touch with us.